Measured building performance
Blower Door and airtightness tests.
Real project results documented under controlled pressurisation and depressurisation.

PH X-1 · Florina's First Certified Passive House
The final evaluation under depressurisation and pressurisation at 50 Pa recorded an average air-change rate n50 of 0.39 1/h, an average airflow V50 of 143 m³/h and an average envelope air permeability q50 of 0.98 m³/(h·m²).
View measured results →
Certified Passive House in Kaisariani, Edessa
The final test recorded an average n50 value of 0.58 1/h, with 0.57 1/h under depressurisation and 0.59 1/h under pressurisation. The average airflow V50 was 229 m³/h and the air permeability q50 was 1.62 m³/(h·m²).
View measured results →
Passive House Project in Ptolemaida
The preliminary airtightness test recorded an average n50 value of 0.44 1/h, with 0.43 1/h under depressurisation and 0.45 1/h under pressurisation. The average airflow V50 was 344 m³/h and the air permeability q50 was 0.86 m³/(h·m²).
View measured results →
Large-scale Airtightness Test at the Interbalkan Medical Center
Participation in the specialist support team for a large-scale Blower Door test, including preparation and real-time measurement support.
View measured results →Contact