Measured building performance

Blower Door and airtightness tests.

Real project results documented under controlled pressurisation and depressurisation.

Airtightness test — Florina
Florina

PH X-1 · Florina's First Certified Passive House

The final evaluation under depressurisation and pressurisation at 50 Pa recorded an average air-change rate n50 of 0.39 1/h, an average airflow V50 of 143 m³/h and an average envelope air permeability q50 of 0.98 m³/(h·m²).

View measured results →
Airtightness test — Kaisariani, Edessa
Kaisariani, Edessa

Certified Passive House in Kaisariani, Edessa

The final test recorded an average n50 value of 0.58 1/h, with 0.57 1/h under depressurisation and 0.59 1/h under pressurisation. The average airflow V50 was 229 m³/h and the air permeability q50 was 1.62 m³/(h·m²).

View measured results →
Airtightness test — Ptolemaida
Ptolemaida

Passive House Project in Ptolemaida

The preliminary airtightness test recorded an average n50 value of 0.44 1/h, with 0.43 1/h under depressurisation and 0.45 1/h under pressurisation. The average airflow V50 was 344 m³/h and the air permeability q50 was 0.86 m³/(h·m²).

View measured results →
Airtightness test — Interbalkan Medical Center · Thessaloniki
Interbalkan Medical Center · Thessaloniki

Large-scale Airtightness Test at the Interbalkan Medical Center

Participation in the specialist support team for a large-scale Blower Door test, including preparation and real-time measurement support.

View measured results →

Contact

Planning a project that deserves to perform better?

Business details

Company
XK Passive House & Engineers Team E.E.
Address
6 Aristotelous & Kioutachias, Florina, Greece
Hours
Monday–Friday 09:00–13:00
Until 20:00 by appointment
Principal engineer
Konstantinos Chatzopoulos
Civil Engineer
Directions on Google Maps →
Open directions to our office →