Blower Door Test · Kaisariani, Edessa
Verified airtightness of the building envelope.
The final test recorded an average n50 value of 0.58 1/h, with 0.57 1/h under depressurisation and 0.59 1/h under pressurisation. The average airflow V50 was 229 m³/h and the air permeability q50 was 1.62 m³/(h·m²).

Measured at 50 Pa
Actual test results
Average n500,58 1/h
Average V50229 m³/h
Average q501,62 m³/(h·m²)
Test documentation
Equipment, inspection and results.